info on: Portable Petrol and Diesel Generators, Inverter Generators, Tractor Pacs, Welders

LLT15/3

Print Specs         Email Colleague
LLT15/3 - <b>15 kVA, 3 Phase, Lister Petter powered, open standby generating set with 90 litre fuel tank, Crossley alternator and remote start/stop controller. </b>
15 kVA, 3 Phase, Lister Petter powered, open standby generating set with 90 litre fuel tank, Crossley alternator and remote start/stop controller.

Specifications

Power Rating: 15 kVA
Alternator Model: Crossley SLG Series
Engine Model: LISTER PETTER TR2
Starter Voltage: 12 V
Frequency: 50 Hz
Cylinder No.: 2
Cubic Capacity: 1.55 L
Bore / Stroke: 98 x 102 mm
Compression Ratio: 15.5 : 1
Aspiration: Natural
Flywheel Max. Cont. Power: 11 kW
Starting System: Electric
Fuel Tank Capacity: 90 L
Approx. Fuel Consumption (1hr cont.): 3.1 L/hr
Approx. Fuel Consumption (1hr standby): 3.4 L/hr
Fuel Type: Diesel
Diam.: 1400 x 760 x 1200 mm (L x W x H)
Weight: 430 kg

 
BUILD SCHEDULE

Standby: kVA @ 0.8p.f. These ratings are applicable for supplying continuous electrical power (at variable loads) in the event of a utility power failure. No overload is permitted on these ratings. Minimum output from alternators are peak continuous rated*

Continuous: kVA @ 0.8 p.f. Available for continuous electrical output. There is no hour limitation. 10% overload is available 1 hour in 12. The generating set and this specification is designed for environmental conditions of up to 27°C, up to 152.4m above sea level and up to 60% relative humidity.

Contact us for ratings outside the specified range.

CONTROL SYSTEM

Key start/stop with following meters:

  • Oil Pressure, Oil Temp, Motor Temp, Frequency, Volts and Amps
  • Shut Down for low oil
  • Emergency stop button
  • Output circuit breaker

ACCESSORIES

  • Muffler, stainless steel exhaust flex (20 KVA and above) and clamps, battery and leads, day fuel tank.
  • Oil and coolant (within engine).
  • Circuit breaker and display for Amps, Volts and Frequency for all sets.

OPTIONS

  • Mains failure control system instead of standard remote control system with mains failure relay, and static battery charger (mains supplied).
  • Changeover contactors in separate cubicle.
  • Constant potential (static) battery charger fitted to key start/stop system or remote start/stop system.
  • Jacket Heater - Thermostatically controlled heater supplied and fitted to maintain engine coolant temperature at approximately 40°C.




Above ratings are applicable for supplying continuous electrical power at variable load in the event of a utility power failure. No overload is permitted. Standard reference conditions 27°C (80°F) Air Inlet Temp, 152.4 m (500 ft) ASL. All engine performance data based on the above mentioned maximum continuous ratings. Fuel consumption data at full load with diesel fuel with a specific gravity of 0.85 and conforming to BS2869:1988, Class A2. Generating set picture may include accessories. One year warranty applies to all W&C Gensets. Specification details may change without notice.
 
Home  |   Petrol Portable Generators  |   Diesel Portable Generators  |   Mine Spec Diesel Generators  |   Welders / Multi-Power Packs  |   Multi-Power Packs  |   Battery Chargers / Starters  |   Water Master Pumps  |   Trailer Mounted Water Tanks  |   Accessories  |   Large Diesel Generators  |   Tractor Pacs  |   Yamaha Products  |   Inverter Generators  |   Downloads  |   FAQ's  |   About Us  |   News  |   Terms & Conditions  |   Privacy Policy  |   Contact Us  |   Sitemap  

Find Us: Generators, Honda Generators, Honda Generators for Sale, Yamaha Generators, Yamaha Generators Australia, Yamaha Inverter Generator Inverter Generator, Inverter Generators, Portable Generators, Inverter Generators for Sale, Portable Inverter Generator, Water Pumps, Fire Fighting Pumps, Water Pumps Australia, Petrol Water Pumps.